How it works
A reading in bar is converted to psig at 14.5038 psi per bar. The hydrogen factor, in SCF per cubic foot of water volume at 70 °F, is read from a table in 25 psi steps from 0 to 10,000 psig and interpolated in a straight line between steps. Above 10,000 psig the 10,000 psig value is used.
Gas in the trailer is the factor times the water volume times 530 ÷ (460 + gas temperature in °F), which is 1 at 70 °F. Hydrogen used is the gas at delivery minus the gas at return, and kilograms are SCF ÷ 423.3 unless you change it. Rated full capacity is the gas at the full fill pressure at 70 °F.
Sources: N.E. Bjork for 0 to 5,000 psig, and NBS Technical Note 1079 for 5,000 to 10,000 psig.